LOW VOLTAGE POWER CABLES

NYY / YVV - Single Core
Technical Features

0,6/1 kV PVC insulated, single core cables with copper conductor.

Construction Cu / Pvc / Pvc 
Certification / Standard TSE / TS IEC60502-1
Application Area Used as lighting and power distribution cable, installed in areas where severe mechanical stress is avoided. Can be laid in doors,out-doors,buried or in cable tranches
Max. operating temperature +70°C
Max. curcuit temperature 160°C
Min. bending radius 15xD
Nominal Cross Section (mm²) Overall Diameter (mm) Net Weight (kg/km) approx. Conductor DC resistance at 20°C (ohm/km) max. Current Carrying Capacity in
Ground (A) Air (A)
1x4 re 7 90 4,61 -   45 37
1x6 re 7,70 120 3,08 - - 57 48
1x10 rm 9 170 1,83 - - 78 66
1x16 rm 10 230 1,15 217 107 103 89
1x25 rm 11,50 330 0,727 163 137 137 118
1x35 rm 12,50 430 0,524 195 165 169 145
1x50 rm 14 570 0,387 120 195 206 176
1x70 rm 15,50 780 0,268 287 239 261 224
1x95 rm 18,00 1050 0,193 336 287 321 271
1x120 rm 19,50 1300 0,153 382 326 374 314
1x150 rm 21,00 1600 0,124 428 366 428 361
1x185 rm 24,00 2000 0,0991 483 414 494 412
1x240 rm 27,00 2550 0,0754 561 481 590 484
1x300 rm 30,00 3200 0,0601 632 542 678 549
1x400 rm 33,00 4000 0,047 730 624 817 657