0,6/1 kV PVC insulated, single core cables with copper conductor.
Construction | Cu / Pvc / Pvc |
Certification / Standard | TSE / TS IEC60502-1 |
Application Area | Used as lighting and power distribution cable, installed in areas where severe mechanical stress is avoided. Can be laid in doors,out-doors,buried or in cable tranches |
Max. operating temperature | +70°C |
Max. curcuit temperature | 160°C |
Min. bending radius | 15xD |
Nominal Cross Section (mm²) | Overall Diameter (mm) | Net Weight (kg/km) approx. | Conductor DC resistance at 20°C (ohm/km) max. | Current Carrying Capacity in | |||
---|---|---|---|---|---|---|---|
Ground (A) | Air (A) | ||||||
1x4 re | 7 | 90 | 4,61 | - | 45 | 37 | |
1x6 re | 7,70 | 120 | 3,08 | - | - | 57 | 48 |
1x10 rm | 9 | 170 | 1,83 | - | - | 78 | 66 |
1x16 rm | 10 | 230 | 1,15 | 217 | 107 | 103 | 89 |
1x25 rm | 11,50 | 330 | 0,727 | 163 | 137 | 137 | 118 |
1x35 rm | 12,50 | 430 | 0,524 | 195 | 165 | 169 | 145 |
1x50 rm | 14 | 570 | 0,387 | 120 | 195 | 206 | 176 |
1x70 rm | 15,50 | 780 | 0,268 | 287 | 239 | 261 | 224 |
1x95 rm | 18,00 | 1050 | 0,193 | 336 | 287 | 321 | 271 |
1x120 rm | 19,50 | 1300 | 0,153 | 382 | 326 | 374 | 314 |
1x150 rm | 21,00 | 1600 | 0,124 | 428 | 366 | 428 | 361 |
1x185 rm | 24,00 | 2000 | 0,0991 | 483 | 414 | 494 | 412 |
1x240 rm | 27,00 | 2550 | 0,0754 | 561 | 481 | 590 | 484 |
1x300 rm | 30,00 | 3200 | 0,0601 | 632 | 542 | 678 | 549 |
1x400 rm | 33,00 | 4000 | 0,047 | 730 | 624 | 817 | 657 |