300 / 500 V PVC insulated non-sheathed single core cables.
| Construction | Cu / Pvc |
| Certification / Standard | TS EN 50525-2-31 |
| Application area | In dry rooms,switching and distribution panels for layer in conduit on or under plaster and/or on insulating support above plaster. |
| Max.operating temperature | 70 °C |
| Max.curcuit temperature | 160 °C |
| Min. bending radius | Up to 10 mm2 3xD, 25mm2 and above 25 mm2 6xD |
| NominalCross Section (mm²) | Overall Diameter (mm) | Net Weight (kg/km) yaklaşık | Conductor DC resistance at 20°C (ohm/km) max. | Current Carrying capacity in | |
|---|---|---|---|---|---|
| Ground (A) | Air (A) | ||||
| 0,5 | 2,00 | 8 | 36 | - | 11 |
| 0,75 | 2,20 | 11 | 24,5 | - | 15 |
| 1,00 | 2,30 | 14 | 18,1 | 11 | 19 |