450 / 750 V PVC insulated non-sheathed single core cables.
Construction | Cu / Pvc |
Certification / Standard | TS EN 50525-2-31 |
Application area | In dry rooms,switching and distribution panels for layer in conduit on or under plaster and/or on insulating support above plaster. |
Max.operating temperature | 90°C |
Max.curcuit temperature | 160°C |
Nominal Cross Section (mm2) | Overall Diameter (mm) | Net Weight (kg/km) | Conductor DC resistance at 20°C(ohm/km) max. | Current Carrying Capacity in | |
---|---|---|---|---|---|
Ground (A) | Air (A) | ||||
1,5 re | 2,8 | 20 | 12,1 | 16 | 25 |
2,5 re | 3,3 | 31 | 7,41 | 21 | 34 |
4 re | 3,8 | 46 | 4,61 | 27 | 45 |
6 re | 4,3 | 54 | 3,08 | 35 | 57 |
10 rm | 6,0 | 115 | 1,83 | 48 | 78 |
16 rm | 7,0 | 170 | 1,15 | 65 | 104 |
25 rm | 8,5 | 260 | 0,727 | 88 | 137 |
35 rm | 9,5 | 360 | 0,524 | 110 | 168 |
50 rm | 11,0 | 480 | 0,387 | 140 | 210 |
70 rm | 13,0 | 670 | 0,268 | 175 | 260 |
95 rm | 15,0 | 930 | 0,193 | 210 | 310 |
120 rm | 16,5 | 1160 | 0,153 | 250 | 365 |
150 rm | 18,0 | 1420 | 0,124 | - | 415 |
185 rm | 20,0 | 1780 | 0,0991 | - | 475 |
240 rm | 23,0 | 2330 | 0,0754 | - | 560 |
300 rm | 26,0 | 2930 | 0,0601 | - | 645 |
400 rm | 29,0 | 3750 | 0,047 | - | 770 |