INSTALLATION CABLES&FLEXIBLE WIRES

H07V-R / 6491X
H07V-R 6491X
Technical Features

450 / 750 V PVC insulated non-sheathed single core cables.

Construction Cu / Pvc
Certification / Standard TSE / TS EN 50525-2-31/,  
Application area In dry rooms,switching and distribution panels for layer in conduit on or under plaster and/or on insulating support above plaster.
Max.operating temperature 70°C
Max.curcuit temperature Cross Section ≤ 300 mm 160 °C
Cross Section > 300 mm 140 °C
Eca
Nominal Cross Section (mm2) Overall Diameter (mm) Net Weight (kg/km) Conductor DC resistance at 20°C(ohm/km) max. Current Carrying Capacity in
Ground (A) Air (A)
1,5 2,80 20 12,1 16 25
2,5 3,30 31 7,41 21 34
4 3,80 46 4,61 27 45
6 4,30 54 3,08 35 57
10 6,00 115 1,83 48 78
16 7,00 170 1,15 65 104
25 8,50 260 0,727 88 137
35 9,50 360 0,524 110 168
50 11,00 480 0,387 140 210
70 13,00 670 0,268 175 260
95 15,00 930 0,193 210 310
120 16,50 1160 0,153 250 365
150 18,00 1420 0,124 - 415
185 20,00 1780 0,0991 - 475
240 23,00 2330 0,754 - 560
300 26,00 2930 0,0601 - 645
400 29,00 3750 0,047 - 770