450 / 750 V PVC insulated non-sheathed single core cables.
| Construction | Cu / Pvc |
| Certification / Standard | TSE / TS EN 50525-2-31/, |
| Application area | In dry rooms,switching and distribution panels for layer in conduit on or under plaster and/or on insulating support above plaster. |
| Max.operating temperature | 70°C |
| Max.curcuit temperature | Cross Section ≤ 300 mm 160 °C Cross Section > 300 mm 140 °C |
| Eca |
| Nominal Cross Section (mm2) | Overall Diameter (mm) | Net Weight (kg/km) | Conductor DC resistance at 20°C(ohm/km) max. | Current Carrying Capacity in | |
|---|---|---|---|---|---|
| Ground (A) | Air (A) | ||||
| 1,5 | 2,80 | 20 | 12,1 | 16 | 25 |
| 2,5 | 3,30 | 31 | 7,41 | 21 | 34 |
| 4 | 3,80 | 46 | 4,61 | 27 | 45 |
| 6 | 4,30 | 54 | 3,08 | 35 | 57 |
| 10 | 6,00 | 115 | 1,83 | 48 | 78 |
| 16 | 7,00 | 170 | 1,15 | 65 | 104 |
| 25 | 8,50 | 260 | 0,727 | 88 | 137 |
| 35 | 9,50 | 360 | 0,524 | 110 | 168 |
| 50 | 11,00 | 480 | 0,387 | 140 | 210 |
| 70 | 13,00 | 670 | 0,268 | 175 | 260 |
| 95 | 15,00 | 930 | 0,193 | 210 | 310 |
| 120 | 16,50 | 1160 | 0,153 | 250 | 365 |
| 150 | 18,00 | 1420 | 0,124 | - | 415 |
| 185 | 20,00 | 1780 | 0,0991 | - | 475 |
| 240 | 23,00 | 2330 | 0,754 | - | 560 |
| 300 | 26,00 | 2930 | 0,0601 | - | 645 |
| 400 | 29,00 | 3750 | 0,047 | - | 770 |