CABLES WITH ALUMINIUM CONDUCTOR

NA2XY / AR2V - Single Core
Technical Features

0,6/1 kV XLPE insulated single core cables with copper conductor.

Construction Al / Xlpe / Pvc
Certification / Standard TS IEC60502-1
Application Area These cables have low dielectric loss, used in energy networks with sudden load chances, installed mainly in residential or industrial aress. May be laid outdoors underground or in ducts
Max. operating temperature +90°C
Max. curcuit temperature 250°C
Min. bending radius 15xD
Nominal Cross Section (mm²) Overall Diameter (mm) Net Weight (kg/km) approx. Conductor DC resistance at 20°C(ohm/km) max. Current Carrying Capacity in
Ground (A) Air (A)
1x16 re 8,70 106 1,91 59 48 73 61
1x25 rm 10,90 153 1,20 73 62 89 78
1x35 rm 12,10 195 0,868 90 77 111 96
1x50 rm 13,80 250 0,641 125 110 133 128
1x70 rm 15,50 325 0,443 160 140 173 166
1x95 rm 17,70 435 0,320 195 170 212 203
1x120 rm 16,90 521 0,253 226 197 247 237
1x150 rm 21,70 640 0,206 261 227 287 274
1x185 rm 24,10 785 0,164 298 259 330 316
1x240 rm 27,20 1018 0,125 352 305 392 375
1x300 rm 30,30 1249 0,100 406 351 455 434
1x400 rm 32,00 1633 0,0778 511 472 502 507
1x500 rm 35,4 211 0,0605 591 546 582 590
1x630 rm 37,8 2670 0,0469 679 629 669 680