300 / 500 V PVC insulated PVC sheated flat wiring cables with bare CPC
Construction | Cu / Pvc / Pvc |
Certification / Standard | |
Application Area | In dry locations, fixed lighting installation, in conduits, embedded in plaster or laid walls. |
Max. operating temperature | +70°C |
Max. curcuit temperature | 160°C |
Nominal Cross Section (mm2) | Mean Overall Diameter (mm) | Net Weight (kg/km) approx. | Conductor DC direnci 20°C (ohm/km) max. | Current Carrying Capacity | ||
---|---|---|---|---|---|---|
Lower Limit | Upper Limit | Conduit (A) | Air (A) | |||
1x1+1 re | 4,0x5,1 | 5,2x6,4 | 43 | 18,1/18,1 | 19 | 13 |
1x1,5+1 re | 4,4x5,4 | 5,8x7,0 | 52 | 12,1/18,1 | 24 | 16,5 |
1x1,5+1 rm | 4,4x5,5 | 5,8x7,0 | 52 | 12,1/18,1 | 19 | 13 |
2x1+1 re | 4,0x7,2 | 4,7x8,6 | 67 | 18,1x18,1 | 19 | 13 |
2x1,5+1 re | 4,4x8,2 | 5,4x9,6 | 83 | 12,1/18,1 | 24 | 17 |
2x1,5+1 rm | 4,5x8,4 | 5,6x10,0 | 83 | 12,1/18,1 | 24 | 17 |
2x2,5+1,5 re | 5,2x9,8 | 6,2x11,5 | 122 | 7,41/12,1 | 33 | 23 |
2x2,5+1,5 rm | 5,2x9,8 | 6,6x12,0 | 122 | 7,41/12,1 | 33 | 23 |
2x4+1,5 rm | 5,6x10,5 | 7,2x13 | 166 | 4,61/12,1 | 45 | 30 |
2x6+2,5 rm | 6,4x12,5 | 8,0x15,0 | 229 | 3,08/7,41 | 58 | 38 |
2x10+4 rm | 7,8x15,5 | 9,6x19,0 | 361 | 1,83/4,61 | 80 | 52 |
2x6+6 rm | 9,0x18,0 | 11,0x22,5 | 532 | 1,15/3,08 | 107 | 69 |
3x1+1 re | 4,0x9,6 | 4,7x11,0 | 89 | 18,1/18,1 | 19 | 13 |
3x1,5+1 re | 4,4x10,5 | 5,4x12,5 | 114 | 12,1/18,1 | 24 | 17 |
3x2,5+1 re | 5,2x12,5 | 6,2x14,5 | 162 | 7,41/18,1 | 33 | 23 |
3x4+1,5 rm | 5,8x14,5 | 7,4x18,0 | 239 | 4,61/12,1 | 45 | 30 |
3x6+2,5 rm | 6,4x16,5 | 8,0x22,0 | 321 | 3,08/7,41 | 58 | 38 |
3x10+4 rm | 7,8x21,0 | 9,6x22,5 | 507 | 1,83/4,61 | 80 | 52 |
3x16+6 rm | 9,0x24,5 | 11,0x29,5 | 749 | 1,15/3,08 | 107 | 69 |