FLAT CABLES

TWIN W/EARTH / 624*Y
Technical Features

300 / 500 V PVC insulated PVC sheated flat wiring cables with bare CPC

Construction Cu / Pvc / Pvc
Certification / Standard  
Application Area In dry locations, fixed lighting installation, in conduits, embedded in plaster or laid walls.
Max. operating temperature +70°C
Max. curcuit temperature 160°C
   
Nominal Cross Section (mm2) Mean Overall Diameter (mm) Net Weight (kg/km) approx.  Conductor DC direnci 20°C (ohm/km) max. Current Carrying Capacity
Lower Limit    Upper Limit    Conduit (A) Air (A)
1x1+1 re 4,0x5,1 5,2x6,4 43 18,1/18,1 19 13
1x1,5+1 re 4,4x5,4 5,8x7,0 52 12,1/18,1 24 16,5
1x1,5+1 rm 4,4x5,5 5,8x7,0 52 12,1/18,1 19 13
2x1+1 re 4,0x7,2 4,7x8,6 67 18,1x18,1 19 13
2x1,5+1 re 4,4x8,2 5,4x9,6 83 12,1/18,1 24 17
2x1,5+1 rm 4,5x8,4 5,6x10,0 83 12,1/18,1 24 17
2x2,5+1,5 re 5,2x9,8 6,2x11,5 122 7,41/12,1 33 23
2x2,5+1,5 rm 5,2x9,8 6,6x12,0 122 7,41/12,1 33 23
2x4+1,5 rm 5,6x10,5 7,2x13 166 4,61/12,1 45 30
2x6+2,5 rm 6,4x12,5 8,0x15,0 229 3,08/7,41 58 38
2x10+4 rm 7,8x15,5 9,6x19,0 361 1,83/4,61 80 52
2x6+6 rm 9,0x18,0 11,0x22,5 532 1,15/3,08 107 69
3x1+1 re 4,0x9,6 4,7x11,0 89 18,1/18,1 19 13
3x1,5+1 re 4,4x10,5 5,4x12,5 114 12,1/18,1 24 17
3x2,5+1 re 5,2x12,5 6,2x14,5 162 7,41/18,1 33 23
3x4+1,5 rm 5,8x14,5 7,4x18,0 239 4,61/12,1 45 30
3x6+2,5 rm 6,4x16,5 8,0x22,0 321 3,08/7,41 58 38
3x10+4 rm 7,8x21,0 9,6x22,5 507 1,83/4,61 80 52
3x16+6 rm 9,0x24,5 11,0x29,5 749 1,15/3,08 107 69