0,6/1 kV XLPE insulated single core halogen free, flame retardant armoured cable.
Construction | Cu / Xlpe / Lszh / Awa / Lszh |
Certification / Standard | BS 6724 |
Application Area | Used in energy networks in hotels,schools,tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire. |
Max. operating temperature | +90°C |
Max. curcuit temperature | 250°C |
Min. bending radius | 8xD |
Nominal Cross Section (mm²) | Overall Diameter (mm) | Net Weight (kg/km) approx. | Conductor DC resistance 20°C(ohm/km) max. | Current Carrying Capacity in | |||
---|---|---|---|---|---|---|---|
Ground (A) | Air (A) | ||||||
1x50 | 17,1 | 702 | 0,387 | 251 | 211 | 258 | 208 |
1x70 | 19,4 | 969 | 0,268 | 307 | 259 | 328 | 265 |
1x95 | 21,3 | 1248 | 0,193 | 366 | 310 | 404 | 329 |
1x120 | 23,3 | 1525 | 0,153 | 416 | 352 | 471 | 381 |
1x150 | 25,8 | 1885 | 0,124 | 465 | 396 | 541 | 438 |
1x185 | 27,8 | 2189 | 0,0991 | 526 | 449 | 626 | 507 |
1x240 | 18,8 | 2551 | 0,0754 | 610 | 521 | 749 | 606 |