CABLES WITH ALUMINIUM CONDUCTOR

NA2XY / AR2V - Multi Core
Technical Features

0,6/1 kV XLPE insulated , multi-core cables with copper conductor.

Construction Al / Xlpe / Pvc / Pvc 
Certification / Standard TS IEC60502-1
Application Area These cables have low dielectric loss, used in energy networks with sudden load chances, installed mainly in residential or industrial aress. May be laid outdoors underground or in ducts.
Max. operating temperature +90°C
Max. curcuit temperature 250°C
Min. bending radius 12xD
Nominal Cross Section(mm²) Overall Diameter(mm) Net Weight(kg/km) approx. Conductor DC resistance at 20°C (ohm/km) max. Current Carrying Capasity in
Ground (A) Air (A)
2x10 14,4 292 3,08 - -
2x16 16,6 392 1,91 84 91
2x25 21,0 608 1,20 101 108
2x35 23,4 768 0,868 126 135
2x50 27,0 1016 0,641 154 164
3x10 15,4 338 3,08 - -
3x16 17,6 446 1,91 76 77
3x25 22,3 678 1,20 90 97
3x35 24,9 864 0,868 112 120
3x50 28,8 147 0,641 136 146
3x70 32,7 1500 0,443 174 187
3x95 37,3 2000 0,320 211 227
3x120 41,2 2400 0,253 245 263
3x150 46,0 3000 0,206 283 304
3x185 51,2 3700 0,164 323 347
3x240 58,0 4800 0,125 382 409
3x300 64,9 5950 0,100 440 471
3x16+16 19,5 560 1,91 76 77
3x25+16 24,0 785 1,20/1,91 90 97
3x35+16 26,5 980 0,868/1,91 112 120
3x50+25 31,0 1310 0,641/1,20 136 146
3x70+35 35,0 1700 0,443/0,868 174 187
3x95+50 40,0 2250 0,320/0,641 211 227
3x120+70 44,5 2775 0,253/0,443 245 263
3x150+70 48,7 3240 0,206/0,443 283 304
3x185+95 54,6 4180 0,164/0,320 323 347
3x240+120 61,5 5323 0,125/0,253 382 409
3x300+150 68,5 6625 0,100/0,206 440 471
4x25 24,7 834 1,20 90 97
4x35 27,6 1065 0,868 112 120
4x50 31,9 1400 0,641 136 146
4x70 36,4 1860 0,443 174 187
4x95 41,4 2450 0,320 211 227
4x120 45,7 2940 0,253 245 263
4x150 52,0 3800 0,206 283 304
4x185 57,7 4670 0,164 323 347
4x240 65,6 6100 0,125 382 409
4x300 72,9 7490 0,100 440 471
5x16 23,0 730 1,91 76 77
5x25 26,7 990 1,20 90 97
5x35 30,4 1290 0,868 112 120
5x50 35,4 1735 0,641 136 146
5x70 40,0 2290 0,443 174 187
5x95 46,5 3100 0,320 211 227