0,6/1 kV XLPE insulated single core halogen free, flame retardant cables.
Construction | Cu / Mica tabe / Xlpe / Lszh |
Certification / Standard | TS HD 604 |
Application Area | Used in energy networks in hotels,schools,tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire. |
Max. operating temperature | +90°C |
Max. curcuit temperature | 250°C |
Min. bending radius | 12xD |
Nominal Cross Section (mm2) | Overall Diameter (mm) | Net Weight (kg/km) | Conductor DC resistance at 20°C(ohm/km) max. | Current Carrying Capacity in | |||
---|---|---|---|---|---|---|---|
Toprakta (A) | Havada (A) | ||||||
1x4 | 8 | 92 | 4,61 | 66 | 55 | 56 | 44 |
1x6 | 8,5 | 110 | 3,08 | 82 | 68 | 71 | 57 |
1x10 | 9,5 | 160 | 1,83 | 109 | 90 | 96 | 77 |
1x16 | 10 | 220 | 1,15 | 139 | 115 | 128 | 102 |
1x25 | 11,5 | 315 | 0,727 | 179 | 149 | 173 | 139 |
1x35 | 12,5 | 410 | 0,524 | 213 | 178 | 212 | 170 |
1x50 | 13,5 | 540 | 0,387 | 251 | 211 | 258 | 208 |
1x70 | 16 | 750 | 0,268 | 307 | 259 | 328 | 265 |
1x95 | 17 | 1000 | 0,193 | 366 | 310 | 404 | 329 |
1x120 | 19 | 1250 | 0,153 | 416 | 352 | 471 | 381 |
1x150 | 21 | 1520 | 0,124 | 465 | 396 | 541 | 438 |
1x185 | 23 | 2905 | 0,0991 | 526 | 449 | 626 | 507 |
1x240 | 26 | 2450 | 0,754 | 610 | 521 | 749 | 606 |
1x300 | 29 | 3100 | 0,0601 | 689 | 587 | 864 | 697 |
1x400 | 33 | 3950 | 0,047 | 788 | 669 | 1018 | 816 |