450 / 750 V PVC insulated non-sheathed single core cables.
Construction | Cu / Pvc |
Certificate / Standard | TS EN 50525-2-31 |
Application area | In dry rooms,switching and distribution panels for layer in conduit ,on/or under plaster and/or on insulating support above plaster. |
Max.operating temperature | 90°C |
Max.curcuit temperature | 160°C |
Nominal Cross Section (mm2) | Overall Diameter (mm) | Net Weight (kg/km) | Conductor DC resistance at 20°C (ohm/km) max. | Current Carrying Capacity in | |
---|---|---|---|---|---|
Ground (A) | Air (A) | ||||
1,5 | 2,8 | 20 | 12,1 | 16 | 25 |
2,5 | 3,3 | 31 | 7,41 | 21 | 34 |
4 | 3,8 | 46 | 4,61 | 27 | 45 |
6 | 4,3 | 54 | 3,08 | 35 | 57 |
10 | 6,0 | 115 | 1,83 | 48 | 78 |
16 | 7,0 | 170 | 1,15 | 65 | 104 |
25 | 8,5 | 260 | 0,727 | 88 | 137 |
35 | 9,5 | 360 | 0,524 | 110 | 168 |
50 | 11 | 480 | 0,387 | 140 | 210 |
70 | 13 | 670 | 0,268 | 175 | 260 |
95 | 15 | 930 | 0,193 | 210 | 310 |
120 | 16,5 | 1160 | 0,153 | 250 | 365 |
150 | 18 | 1420 | 0,124 | - | 415 |
185 | 20 | 1780 | 0,0991 | - | 475 |
240 | 23 | 2330 | 0,0754 | - | 560 |
300 | 26 | 2930 | 0,0601 | - | 645 |
400 | 29 | 3750 | 0,0470 | - | 770 |