Technical Features

0,6/1 kV XLPE insulated , single core halogen free, flame retardant cables.

Construction Al / Xlpe / Hffr
Certification / Standard TS HD 604 / IEC 60502-1
Application Area Used in energy networks in hotels,schools,tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire.
Max. operating temperature +90°C
Max. curcuit temperature 250°C
Min. bending radius 15xD
Nominal Cross Section (mm²) Overall Diameter (mm) Net Weight (kg/km) approx.  Conductor DC resistance at 20°C(ohm/km) max. Current Carrying Capacity in
Ground (A) Air (A)
1x16 8,7 106 1,91 76 64 91 77
1x25 10,9 153 1,20 90 84 108 97
1x35 12,1 195 0,868 112 103 135 120
1x50 13,8 250 0,641 154 136 165 159
1x70 15,5 325 0,443 198 174 215 206
1x95 17,7 435 0,320 241 211 264 253
1x120 19,6 521 0,253 280 245 308 296
1x150 21,7 640 0,206 324 283 358 343
1x185 24,1 785 0,164 371 323 413 395
1x240 27,2 1018 1018 439 382 492 471
1x300 30,3 1249 0,100 508 440 571 544
1x400 32,0 1633 0,0778 658 594 628 638
1x500 35,4 211 0,0605 765 692 728 743
1x630 37,8 2670 0,0469 871 791 836 849