0,6/1 kV XLPE insulated , single core halogen free, flame retardant cables.
Construction | Al / Xlpe / Hffr |
Certification / Standard | TS HD 604 / IEC 60502-1 |
Application Area | Used in energy networks in hotels,schools,tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire. |
Max. operating temperature | +90°C |
Max. curcuit temperature | 250°C |
Min. bending radius | 15xD |
Nominal Cross Section (mm²) | Overall Diameter (mm) | Net Weight (kg/km) approx. | Conductor DC resistance at 20°C(ohm/km) max. | Current Carrying Capacity in | |||
---|---|---|---|---|---|---|---|
Ground (A) | Air (A) | ||||||
1x16 | 8,7 | 106 | 1,91 | 76 | 64 | 91 | 77 |
1x25 | 10,9 | 153 | 1,20 | 90 | 84 | 108 | 97 |
1x35 | 12,1 | 195 | 0,868 | 112 | 103 | 135 | 120 |
1x50 | 13,8 | 250 | 0,641 | 154 | 136 | 165 | 159 |
1x70 | 15,5 | 325 | 0,443 | 198 | 174 | 215 | 206 |
1x95 | 17,7 | 435 | 0,320 | 241 | 211 | 264 | 253 |
1x120 | 19,6 | 521 | 0,253 | 280 | 245 | 308 | 296 |
1x150 | 21,7 | 640 | 0,206 | 324 | 283 | 358 | 343 |
1x185 | 24,1 | 785 | 0,164 | 371 | 323 | 413 | 395 |
1x240 | 27,2 | 1018 | 1018 | 439 | 382 | 492 | 471 |
1x300 | 30,3 | 1249 | 0,100 | 508 | 440 | 571 | 544 |
1x400 | 32,0 | 1633 | 0,0778 | 658 | 594 | 628 | 638 |
1x500 | 35,4 | 211 | 0,0605 | 765 | 692 | 728 | 743 |
1x630 | 37,8 | 2670 | 0,0469 | 871 | 791 | 836 | 849 |