CABLES WITH ALUMINIUM CONDUCTOR

YAVV / NAYY - Multi Core
Technical Features

0,6/1 kV PVC insulated,multi-core cables with aluminium conductor.

Construction Al / Pvc / Pvc / Pvc
Certification / Standard TSE / TS IEC60502-1
Application Area Used as lighting and power distribution cable, installed in areas where severe mechanical stress is avoided. Can be laid in doors,out-doors,buried or in cable tranches.
Max. operating temperature +70°C
Max. curcuit temperature 160°C
Min. bending radius 12xD
Nominal Cross Section (mm²) Overall Diameter (mm) Net Weight (kg/km) approx.  Conductor DC resistance 20°C(ohm/km) max. Current Carrying Capacity in
Ground (A) Air (A)
2x10 15,60 348 3,08 - -
2x16 17,80 458 1,91 48 61
2x25 22,20 696 1,2 62 78
2x35 24,60 867 0,868 77 96
2x50 28,60 1165 0,641 92 117
3x10 16,70 406 3,08 - -
3x16 18,90 523 1,91 48 61
3x25 23,60 784 1,2 62 78
3x35 26,20 984 0,868 77 96
3x50 30,50 1322 0,641 92 117
3x70 34 1676 0,443 116 150
3x95 39,5 2278 0,32 139 183
3x120 42,9 2664 0,253 160 212
3x150 47,7 3304 0,206 176 245
3x185 52,9 4053 0,164 199 280
3x240 60,2 5289 0,125 232 330
3x300 67 6508 0,1 265 381
4x16 21,4 677 1,91 48 61
4x25 26,1 964 1,2 62 78
4x35 29 1211 0,868 77 96
4x50 33,8 1625 0,641 92 117
4x70 37,8 2076 0,443 116 150
4x95 43,8 2807 0,32 139 183
4x120 47,7 3298 0,253 160 212
4x150 54 4226 0,206 176 245
4x185 59,7 5152 0,164 199 280
4x240 68 6741 0,125 323 330
4x300 75,3 8230 0,1 265 381
5x10 22,2 728 3,08 - -
5x16 25,2 986 1,91 48 61
5x25 31,8 1448 1,2 62 78
5x35 35,4 1822 0,868 77 96
3x16+10 21 666 1,91/3,08 48 61
3x25+16 25 884 1,20/1,91 62 78
3x35+16 27,6 1093 0,868/1,91 77 96
3x50+25 32,4 1480 0,641/1,2 92 117
3x70+35 36 1864 0,443/0,868 116 150
3x95+50 41,7 2507 0,32/0,641 139 183
3x120+70 45,9 3026 0,253/0,443 160 212
3x150+70 50,1 3537 0,206/0,443 176 245
3x185+95 56,2 4536 0,164/0,320 199 280
2x240+120 63,3 5786 0,125/0,253 232 330
3x300+150 70,3 7174 0,100/0,206 265 381