0,6/1 kV XLPE insulated single core halogen free, flame retardant cables.
| Construction | Cu / Xlpe / Lszh |
| Certification / Standard | TS HD 604 |
| Application Area | Used in energy networks in hotels,schools,tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire. |
| Max. operating temperature | +90°C |
| Max. curcuit temperature | 250°C |
| Min. bending radius | 15xD |
| Nominal Cross Section (mm2) | Overall Diameter (mm) | Net Weight (kg/km) | Conductor DC resistance 20°C (ohm/km) max. | Current Carrying Capacity in | |||
|---|---|---|---|---|---|---|---|
| Ground (A) | Air (A) | ||||||
![]() |
![]() |
![]() |
![]() |
||||
| 1x4 re | 7,00 | 70 | 4,61 | 66 | 55 | 56 | 44 |
| 1x6 re | 7,50 | 85 | 3,08 | 82 | 68 | 71 | 57 |
| 1x10 rm | 8,50 | 130 | 1,83 | 109 | 90 | 96 | 77 |
| 1x16 rm | 9,50 | 200 | 1,15 | 139 | 115 | 128 | 102 |
| 1x25 rm | 11,00 | 300 | 0,727 | 179 | 149 | 173 | 139 |
| 1x35 rm | 12,50 | 400 | 0,52 | 213 | 178 | 212 | 170 |
| 1x50 rm | 13,50 | 500 | 0,387 | 251 | 211 | 258 | 208 |
| 1x70 rm | 15,50 | 750 | 0,268 | 307 | 259 | 328 | 265 |
| 1x95 rm | 17,50 | 950 | 0,193 | 366 | 310 | 404 | 329 |
| 1x120 rm | 19,50 | 1200 | 0,153 | 416 | 352 | 471 | 381 |
| 1x150 rm | 21,50 | 1500 | 0,124 | 465 | 396 | 541 | 438 |
| 1x185 rm | 23,50 | 1850 | 0,0991 | 526 | 449 | 626 | 507 |
| 1x240 rm | 26,50 | 2350 | 0,075 | 610 | 521 | 749 | 606 |
| 1x300 rm | 28,50 | 3000 | 0,0601 | 689 | 587 | 804 | 697 |
| 1x400 rm | 32,50 | 3900 | 0,047 | 788 | 669 | 1018 | 816 |