HALOGEN FREE FIRE RESISTANT CABLES

6491B
Technical Features

450 / 750 V halogen free, flame retardant cables.

Construction Cu/XL-LSZH
Certification / Standard  
Application Area Used in energy networks in refineries, minesi hotels, schools, tunnels, h,igh constructions, hospitals, power plants, data processing centers, business center where there is a risk of fire.
Max. operating temperature +90°C
Max. curcuit temperature 250°C
Min. bending radius 10 mm2 'ye kadar 3xD, 25 mm2 ve üzeri 6xD
Nominal Cross Section (mm2) Overall Diameter (mm) Net Weight (kg/km)  Conductor DC resistance 20°C (ohm/km) max. Current Carrying Capacity in
Ground (A) Air (A)
1,5  2,90 20 12,1 16 24
2,5 3,50 35 7,41 21 32
4 4,00 50 4,61 27 43
6 4,50 65 3,08 34 54
10 6,00 110 1,83 47 74
16 7,00 170 1,15 64 99
25 8,50 260 0,727 86 134
35 9,50 350 0,524 107 159
50 11,50 500 0,387 164 199
70 13,00 690 0,268 177 246
95 15,00 930 0,193 237 294
120 16,60 1160 0,153 - 354
150 18,60 1450 0,124 - 393
185 21,00 1800 0,0991 - 451
240 24,00 2350 0,0754 - 529
300 27,00 2920 0,0601 - 611
400 31,00 3800 0,047 - 729