SOLAR CABLES

PV1-F
Technical Features

0,6/1 kV HFFR insulated,HFFR sheated single core solar cable with tin plated flexible copper conductor

Construction Cu/HFFR/HFFR
Certification / Standard 2Pfg-1169
Application Area In interconnection of the photovoltaic systems in solar energy breeder, solar cells, solar panels
Max. operating temperature 90 °C
Max. curcuit temperature 200 °C
Min. bending radius 5xD
Nominal Cross Section (mm²) Overall Diameter (mm) Net Weight (kg/km) approx. Conductor DC resistance at 20°C(ohm/km) max. Current Carrying Capacity in
Air (A)
2,5 4,9 45 8,21 41
4 5,4 60 5,09 55
6 5,9 80 3,39 70
16 8,7 180 1,24 132
25 10,35 280 0,795 176
35 11,45 370 0,565 218
50 12,9 520 0,393 276
70 14,8 750 0,277 347
95 16,6 980 0,21 416
120 18,2 1150 0,164 488