450 / 750 V PVC insulated non-sheathed single core cables.
| Construction | Cu / Pvc |
| Certificate / Standard | TS EN 50525-2-31 |
| Application area | For protected installation and lighting fitting and also for in conduit , on and under plaster. |
| Max.operating temperature | 90 °C |
| Max.curcuit temperature | 160 °C |
| Nominal Cross Section (mm2) | Overall Diameter (mm) | Net Weight (kg/km) | Conductor DC resistance at 20°C (ohm/km) max. | Current Carrying Capacity in | |
|---|---|---|---|---|---|
| Ground (A) | Air (A) | ||||
| 1,5 | 3,0 | 20 | 13,3 | 15 | 24 |
| 2,5 | 3,6 | 32 | 7,98 | 20 | 32 |
| 4 | 4,2 | 48 | 4,95 | 25 | 41 |
| 6 | 4,8 | 66 | 3,3 | 33 | 53 |
| 10 | 6,3 | 110 | 1,91 | 45 | 73 |
| 16 | 7,3 | 170 | 1,21 | 61 | 98 |
| 25 | 9,8 | 270 | 0,78 | 83 | 129 |
| 35 | 11,0 | 360 | 0,554 | 103 | 158 |
| 50 | 13,0 | 510 | 0,386 | 132 | 198 |
| 70 | 15,0 | 700 | 0,272 | 165 | 245 |
| 95 | 17,5 | 930 | 0,206 | 197 | 292 |
| 120 | 19,5 | 1175 | 0,161 | 235 | 344 |
| 150 | 21,5 | 1450 | 0,129 | - | 391 |
| 185 | 24,0 | 1770 | 0,106 | - | 448 |
| 240 | 27,0 | 2250 | 0,0801 | - | 528 |